| Sign In | Join Free | My infospaceinc.com |
|
Price : USD 410/Unit
Packaging Details : original packing
Duty Basis : elow 10 Percent ED; Maximum 10 Seconds
Model Number : CDBR-4030B
Reference Motor Output : 40 HP / 30 kW with One Unit in Legacy Selection Table
Supply Ability : 10Units per Month
AC Drive Voltage Range : 380 to 460 VAC
Maximum Discharge Current : 40 A Peak
Payment Terms : D/A, D/P, T/T, Western Union, MoneyGram,
DC Bus Operating Range : 460 to 800 VDC Peak
Delivery Time : 3-5Days
Product Type : Dynamic Braking Transistor Module
Brand Name : YASKAWA
Heat Loss : 54 W
Approximate Dimensions : 150 x 140 x 138.5 mm
Rated Discharge Current : 15 A
Braking Start Voltage Settings : 630 / 660 / 690 / 730 / 760 VDC
Place of Origin : USA
MOQ : 1
Protective Configuration : Wall-Mounted Enclosed Type
Model : CDBR-4030B
External Braking Resistor : Required
Current D-Series Upgrade Candidate : CDBR-40300D
The Yaskawa CDBR-4030B is a previous-generation dynamic braking transistor unit for 380 to 460 VAC-class industrial drive systems. It is rated for 15 A discharge current with a maximum peak discharge current of 40 A.
The module operates with an external braking resistor to dissipate regenerated DC bus energy during deceleration. It is not a resistor unit and should not be ordered without confirming the existing resistor and thermal-protection arrangement.
| Manufacturer | Yaskawa Electric |
| Series | CDBR-B |
| Model | CDBR-4030B |
| Product Type | Dynamic Braking Transistor Unit |
| Product Generation | Previous Generation |
| AC Drive Voltage Range | 380 to 460 VAC |
| DC Bus Range | 460 to 800 VDC Peak |
| Rated Discharge Current | 15 A |
| Maximum Discharge Current | 40 A Peak |
| Duty Reference | Below 10 Percent ED; Maximum 10 Seconds |
| Braking Start Settings | 630 / 660 / 690 / 730 / 760 VDC |
| Reference Motor Output | 40 HP / 30 kW with One Unit in Legacy Selection Table |
| Heat Loss | 54 W |
| Protective Configuration | Wall-Mounted Enclosed Type |
| Approximate Dimensions | 150 x 140 x 138.5 mm |
| Current Upgrade Candidate | CDBR-40300D |
The CDBR-4030B was designed for compatible previous-generation Yaskawa industrial drives. Confirm the full drive model and wiring diagram because products with the same 400 V voltage class do not automatically use the same braking module.
Typical applications include machine tools, packaging equipment, conveyors, winders, hoists, centrifuges and other machinery requiring shorter stopping times or control of regenerated energy.
Before replacing the unit, check the voltage-selection connector, master or slave setting, DC bus terminals, control terminals, resistor value, resistor thermal contact and enclosure ventilation.
The legacy application table associates one CDBR-4030B with a 40 HP or 30 kW drive under specified braking conditions. Higher-capacity arrangements used multiple units, but the quantity must be determined from the approved selection table.
CDBR-40300D is the corresponding current 15 Arms D-series upgrade candidate. It should not be installed as a direct physical replacement until the mounting dimensions, terminal arrangement, control wiring and resistor compatibility have been reviewed.
Related models include CDBR-4045B, CDBR-4090B, CDBR-4220B and the newer CDBR-40300D or CDBR-4030D.
Please provide clear photographs of the nameplate and terminals, the complete inverter model, braking resistor information and the required braking cycle. Availability and product condition must be confirmed for each quotation because CDBR-4030B is a previous-generation model.
|
|
Yaskawa CDBR-4030B 480V 15A Legacy Dynamic Braking Unit for AC Drives Images |